Hardware Configuration

Basic Dimension 40ft’container(12192*2438*2896mm)
Overall Weight 12 Ton
Standard Power 240KW
IT Power 210KW
Rated Voltage and Frequency 415V±5%,50/60HZ
Number of Tanks Four
Single TANK Specifications 36U
Compatible Devices Immersion servers
Safety Standards UL/CE
Heat Dissipation Method Internal circulation: single-phase immersion External circulation: cooling tower
Fire control Heptafluoropropane (70L)
Deployment environment 32℃ Wet Bulb Temperature 50℃ 30%RH
Power Main Switch UL:400A/3P 65KA
Branch Switch UL:80A/3P
Rated Current 380A
PDU AC250V C19*18+C13*1
Power System TN-S(3L+N+PE)
Inlet Cable L1~L3: (single core cable 600kcMil*1)*3 N Single-core cable 600kcMil*1 PE single-core cable 600kcMil*1
UPS [50KVA*(5+1)]300KVA
Battery Backup Time 5 mins
Power supply method Dual utility + generator
HVAC Cooling Tower Capacity 300KW
Unit Size 2200*2400*2480mm(L*W*H)
Shipping Weight 1.6 Ton
Operating Weight 2.8 Ton
External Circulation Coolant Water
Water Consumption 0.3~0.4m³/h
Internal Circulation Coolant Cooling Oil (Hydrocarbon Recommended)
Minimum Coolant Amount 3.8m³1000Gallon us
Inlet/Outlet Water Temperature Miner @normal mode 50/60℃122℉/140℉
Replenishment Pipe Diameter DN25
Sewage Pipe Diameter DN50
Air-conditioning cooling capacity 10KW+10KW
Heat Recycle Rated Thermal Efficiency ≥97%
Heating Area 2328~11640㎡(Greenhouse- Apartment House)
Heat Recycle Inlet/Outlet Water Temperature 55/45℃131℉/113℉
Heating Inlet Pipe Diameter DN100
Heating Outlet Pipe Diameter DN100